- Stock: 1
- Model: DZD006505
Functions:
1. Over voltage protection
2. Under voltage protection
3. Over current protection
4. Automatic recovery
5. Voltage display (voltage measurement)
6. Current display (current measurement)
7. Voltage calibration: voltage +-10% adjustable. A13
8. Restore factory settings: press the DOWN button for more than 12s
9. Fault inquiry: press the UP button for more than 12S
Product parameters:
1. Model number: TOVPD1-60-EC
2. Power supply: 230VAC 50/60Hz
3.Max. Loading power: 1~40A adjustable (default: 40A)
1~63A adjustable (default: 63A)
4. Overvoltage protection value range: 230V~300~OFF (default: 270V)
Overvoltage recovery voltage range: 225V--295V (default: 250V)
Overvoltage protection action time: 0.1s~30s (default: 0.5s)
Overvoltage recovery delay time: 1s~500s (default: 30s)
5. Undervoltage protection value range: 140V-210V-OFF (default: 170V)
Undervoltage recovery voltage range: 145V--215V (default: 190V)
Undervoltage protection action time: 0.1s~30s (default: 0.5s)
Undervoltage R Ecovery delay time: 1s~500s (default: 30s)
6. Over-current adjustment range: 1-40A (default: 20A) 1-63A (default: 40A)
Over-current action range: 0.1~30 second (default: 0.5s)
Over-current R Ecovery delay time: 1s~500s (default: 30s)
7.Power-on delay time: 1s~500s (default: 10s)
9. Power consumption: <2W
10. Electrical machinery life: 100,000 times
11.Installation: 35mm DIN rail
GRBL